Reinforcing Fault Ride Through Capability of Grid Forming Voltage Source Converters Using an Enhanced Voltage Control Scheme
Type
JournalPaper
Keywords
Asymmetrical short circuit fault, current reference limiter, distribution system, fault ride through, grid forming converters, voltage source converters, voltage controller
Year
2018
Journal IEEE TRANSACTIONS ON POWER DELIVERY
DOI
Researchers Fariborz Zarei ، Hossein Mokhtari ، Mohamad Amin Ghasemi ، frede Blaabjerg

Abstract

Medium power distributed energy resources (DERs) are commonly connected to medium voltage distribution systems via voltage source converters (VSCs). Several guidelines and standards have been developed to establish the needed criteria and requirements for DERs interconnections. In this respect, it is preferred to reinforce the VSC fault ride through (FRT) capability, which considerably minimizes the DG outage period and reconnection time and results in a resilient system against short circuits. Considering the significant number of asymmetrical faults in distribution systems, the VSC response in such conditions must be investigated, and consequently, its FRT capability must be reinforced. In this paper firstly a comprehensive review on existing FRT methods has been presented and discussed. Accordingly, an adaptive virtual impedance-based voltage reference generation method is proposed, which enhances the VSC behavior under short circuits and increases the VSC FRT capability. Also, a fast sinusoidal current reference limiter is proposed to improve the performance. To evaluate the performance of the proposed scheme, state space analysis is presented, and a complete set of simulations is performed in PSCAD/EMTDC environment. Also, a comparison with the conventional method is presented